Evaluation of Effects of PermaFrost Treatment for Rooftop AC Units
Energy Consumption at Bank of America in Austin, Texas
Prepared by Tony Bloom, PE - June 2003
INTRODUCTION
This test monitored power usage in order to determine the kilowatt-hour
consumption of RTU-1 (Roof Top Unit) and RTU-2 air conditioning systems at
the Bank of America branch at Loop 360 and US 183 in Austin Texas.
METHODOLOGY
Energy consumption of both units was monitored simultaneously for one
week before and one week after treatment with PermaFrost. The first and last
days of monitoring were partial days and/or included the period while
PermaFrost was being installed. Therefore, these days were not included in
the report.
OBSERVATIONS
- Total energy consumption before permafrost: 654 KWH
- Total energy consumption after permafrost: 524 KWH
- The net reduction in energy consumption was 20% for the period.
- The weather conditions during the monitoring period was variable,
however, the before and after weather conditions were similar.
RTU- 1 & RTU- 2 Before and After PermaFrost
Total kWH Consumption Per Week
|